Utilisation category |
AC-3 AC-3e AC-1 AC-4 |
poles description |
3P |
power pole contact composition |
3 NO |
[Ue] rated operational voltage |
Power circuit <= 690 V AC <= 400 Hz Signalling circuit <= 690 V AC <= 400 Hz |
[Ie] rated operational current |
9 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3 for power circuit 9 A (at <140.0000000000 °F (60 °C)) at <= 440 V AC AC-3e for power circuit 20 A (at <140.0000000000 °F (60 °C)) at <= 690 V AC AC-1 for power circuit |
Control circuit type |
DC standard |
[Uc] control circuit voltage |
48 V DC |
Motor power kW |
2.2 kW 220...230 V AC 50/60 Hz AC-3 4 kW 380...415 V AC 50/60 Hz AC-3 4 kW 440/690 V AC 50/60 Hz AC-3 2.2 kW 220...230 V AC 50/60 Hz AC-3e 4 kW 380...415 V AC 50/60 Hz AC-3e 4 kW 440/690 V AC 50/60 Hz AC-3e 2.2 kW 220...230 V AC 50/60 Hz AC-4 4 kW 380...415 V AC 50/60 Hz AC-4 4 kW 440/690 V AC 50/60 Hz AC-4 |
Auxiliary contact composition |
1 NC |
[Uimp] rated impulse withstand voltage |
8 kV |
Overvoltage category |
III |
[Ith] conventional free air thermal current |
20 A (at 140.0000000000 °F (60 °C)) for power circuit 10 A (at 122.0000000000 °F (50 °C)) for signalling circuit |
Irms rated making capacity |
110 A AC for power circuit conforming to IEC 60947 110 A AC for signalling circuit conforming to IEC 60947 |
Rated breaking capacity |
110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947 |
[Icw] rated short-time withstand current |
90 A 122.0000000000 °F (50 °C) - 1 s for power circuit 85 A 122.0000000000 °F (50 °C) - 5 s for power circuit 80 A 122.0000000000 °F (50 °C) - 10 s for power circuit 60 A 122.0000000000 °F (50 °C) - 30 s for power circuit 45 A 122.0000000000 °F (50 °C) - 1 min for power circuit 40 A 122.0000000000 °F (50 °C) - 3 min for power circuit 20 A 122.0000000000 °F (50 °C) - >= 15 min for power circuit 80 A - 1 s for signalling circuit 90 A - 500 ms for signalling circuit 110 A - 100 ms for signalling circuit |
Associated fuse rating |
25 A gG at <= 440 V for power circuit 25 A aM for power circuit 10 A gG for signalling circuit conforming to IEC 60947 10 A gG for signalling circuit conforming to VDE 0660 |
Average impedance |
3 mOhm - Ith 20 A 50 Hz for power circuit |
[Ui] rated insulation voltage |
Power circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-4-1 Signalling circuit 690 V IEC 60947-5-1 Signalling circuit 600 V UL 508 Power circuit 600 V CSA C22.2 No 14 Signalling circuit 600 V CSA C22.2 No 14 |
Insulation resistance |
> 10 MOhm for signalling circuit |
Inrush power in W |
3 W 68.0000000000 °F (20 °C)) |
Hold-in power consumption in W |
3 W 68.0000000000 °F (20 °C) |
Heat dissipation |
1.3 W |
Control circuit voltage limits |
Operational: 0.8...1.15 Uc (at <122.0000000000 °F (50 °C)) Drop-out: >= 0.10 Uc (at <122.0000000000 °F (50 °C)) |
Connections - terminals |
Screw clamp terminals 1 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 1 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 1 0.0005…0.004 in² (0.34…2.5 mm²)flexible with cable end screw clamp terminals 2 0.002…0.006 in² (1.5…4 mm²)solid screw clamp terminals 2 0.001…0.006 in² (0.75…4 mm²)flexible without cable end screw clamp terminals 2 0.0005…0.002 in² (0.34…1.5 mm²)flexible with cable end Power circuit screw clamp terminals 2 0.002 in² (1.5 mm²)flexible with cable end |
Maximum operating rate |
3600 cyc/h |
Auxiliary contacts type |
Instantaneous 1 NC |
Minimum switching current |
5 mA for signalling circuit |
Minimum switching voltage |
17 V for signalling circuit |
Mounting Support |
Plate Rail |
Tightening torque |
7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals Philips No 2 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals flat Ø 6 mm 7.08…11.5 lbf.in (0.8…1.3 N.m) screw clamp terminals pozidriv No 2 |
Operating time |
30...40 ms coil energisation and NO closing 10 ms coil de-energisation and NO opening |
Safety reliability level |
B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
Mechanical durability |
10 Mcycles |
Electrical durability |
1.3 Mcycles 9 A AC-3 <= 440 V 1.3 Mcycles 9 A AC-3e <= 440 V 0.16 Mcycles 20 A AC-1 <= 690 V 0.02 Mcycles 54 A AC-4 <= 440 V |
Height |
2.3 in (58 mm) |
Width |
1.8 in (45 mm) |
Depth |
2.2 in (57 mm) |
Net Weight |
0.496 lb(US) (0.225 kg) |